Micro-Electronics and Electronics Applications
The demands for this sector are very different to that of pharmaceutical manufacturing. Contamination issues are more focused on airborne particulates, and higher air change rates & laminar airflow are demanded.
|
MSS Electronics Application Cleanroom |
|
Cleanliness of the facility, free from particulates generated by people and conditioned air, is paramount. It would be normal practice to be fully gowned, and enter the facility through a high velocity HEPA filtered air shower to remove residual particulates.
To achieve the cleanliness levels as low as ISO 4 (Federal Standard 209E Class 10) requires many air changes per hour and laminar airflow. To achieve this requires a supply plenum; a ceiling with filters (or fan filter units) usually covering 100% of the area; plus a raised floor with sub-floor plenum. The conditioned air is re-circulated via the sub-floor plenum, connected by return air chases fitted with localised heating/cooling (as required).
|
||
|
||
|
||